12
2.4 Smart Inverter Functions:
The CPS SCA50KTL-DO/US-480 and CPS SCA60KTL-DO/US-480 3-Phase
String Inverters employ Smart Inverter (Grid Support) Functions in compliance
with UL1741-SA, SA8-SA15. The default activation status is indicated below.
Smart Inverter Function IEEE1547-2014 Rule 21 ISO-NE
Anti-islanding Enabled Enabled Enabled
Low/High Voltage Ride-
Through
N/A Enabled Enabled
Low/High Frequency Ride-
Through
N/A Enabled Enabled
Dynamic Volt/VAR Operation N/A Enabled Disabled
Ramp Rate N/A Enabled Enabled
Fixed Power Factor N/A Disabled Disabled
Reconnect by “Soft-Start” N/A Enabled Enabled
Frequency-Watt N/A Enabled Disabled
Volt/Watt N/A Enabled Disabled