119
Table 7-3 LCD Troubleshooting ALARM
Type Error/State Fault Description / Instruction
Alarm
TempSensorErr
Definition: Prompt detection of abnormal
temperature
1. Temperature Sensor socket connecter has poor
contact
2. Temperature Sensor is damaged
1. Observe temperature display
2. Switch off exernal AC disconnect, then back on
to reboot the system;
3. Contact post-sales service if not corrected
CommErr
Definition: Communication inside inverter fails
Possible causes:
Terminal block connecters of internal communication
wires have poor contact
1. Observe for 5 minutes to see whether the alarm
will be eliminated automatically
2. Switch off exernal AC disconnect, then back on
to reboot the system
3. Contact post-sales service if not corrected
ExtFanErr
Definition: Cooling fan failure
1. Fan is blocked
2. Fan service life has expired
3. Fan socket connecter has poor contact
1. Observe for 5 minutes to see whether the alarm
will be eliminated automatically
2. Check for foreign objects on fan blades;
3. Switch off exernal AC disconnect, then back on
to reboot the system
4. Contact post-sales service if not corrected
EepromErr
Definition: Internal alarm
Possible causes:
Internal memory has a problem
1. Observe for 5 minutes to see whether the alarm
will be eliminated automatically
2. Contact post-sales service if not corrected