ENGLISH
64
Setting auxiliary setpoint input function
The signal that enables an auxiliary setpoint can be supplied on any of the 4 inputs (for the electrical connections, refer to the control
unit manual). The auxiliary setpoint is obtained by setting the Ix parameter relating to the input on which the connection has been made,
in accordance with Table 16. Example: to use Paux 2 set I2 on 3 or 4 and use input 2 on the control unit; in this condition, if input 2 is
energized, pressure Paux 2 will be produced and the display will show P2. The auxiliary setpoint function modifies the system setpoint
from pressure SP (see par. 13.2.3 Setpoint Menu) to pressure Pi, where is represents the input used. In this way, as well as SP, four
other pressures are available, P1, P2, P3, P4.
When this function is active the symbol Pi is shown in the STATUS line on the main page.
For the system to work with the auxiliary setpoint, the input must be active for at least 1sec. When you are working with the auxiliary
setpoint, to return to working with setpoint SP, the input must not be active for at least 1 sec. The behaviour of the function is summed
up in Table 16.
When several auxiliary setpoint functions are configured at the same time on different inputs, the system will show Pi when at least one
function is activated. For simultaneous activations, the pressure achieved will be the lowest of those with the active input. The alarm is
removed when no input is activated.
Behaviour of the auxiliary setpoint function depending on Ix and on the input
Input configuration Input status Operation
3
Active with high signal on
input (NO)
i-th auxiliary setpoint not active
i-th auxiliary setpoint active
4
Active with low signal on
input (NC)
i-th auxiliary setpoint active
i-th auxiliary setpoint not active
Table 16: Auxiliary setpoint
Setting system disabling and fault reset
The signal that enables the system can be supplied to any input (for the electrical connections refer to the control unit manual). The
system disabling function is obtained by setting the parameter Ix, relating to the input to which the signal to be used to disable the system
is connected, on one of the values shown in Table 17.
When the function is active, the system shuts down completely and the F3 symbol appears on the main page.
When several system disabling functions are configured at the same time on different inputs, the system will indicate F3 when at least
one function is activated and will remove the alarm when none is activated. For the system to work with the disable function, the input
must be active for at least 1 sec. When the system is disabled, for the function to be deactivated (re-enabling the system), the input
must not be active for at least 1 sec. The behaviour of the function is summed up in Table 17.
When several disable functions are configured at the same time on different inputs, the system will show F3 when at least one function is
activated. The alarm is removed when no input is activated. This function also allows the resetting of any faults present, see Table 17.
Behaviour of the system disabling and fault reset function depending on Ix and on the input
Input configuration Input status Operation
5 Active with high signal on input (NO)
6 Active with low signal on input (NC)
7 Active with high signal on input (NO)
Present
Motor disabled +
fault reset
F3
8 Active with low signal on input (NC)
Absent
Motor disabled +
fault reset
F3
9 Active with high signal on input (NO)
Table 17: Disabling system restore and fault
Setup of the outputs OUT1, OUT2
This section shows the functions and possible configurations of outputs OUT1 and OUT2 of the I/O control unit, with wireless
connection to the device, set by means of parameters O1 and O2. For the electrical connections, refer to the control unit manual.
The factory configurations can be seen inTable 18.