10 | Configuration
Installer reference guide
160
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Setpoint mode
The setpoint mode of the additional zone can be independently set from the
setpoint mode of the main zone.
See "Setpoint mode"[4150].
# Code Description
[3.4] N/A Setpoint mode
Fixed
WD heating, fixed cooling
Weather dependent
WD curve type
The weather dependent curve can be defined using the 2-points method or the
Slope-Offset method.
Also see "10.4.22-points curve"[4142] and "10.4.3Slope-offset curve"[4143].
The curve type in the menu of the additional zone is read only. It corresponds to
the curve type that is in use for the main zone. Thus, changing the curve type for
the additional zone must be done in the menu of the main zone: [2.E] WD curve
type.
Also see "10.5.3Main zone"[4150].
# Code Description
[2.E] N/A 2-points
Slope-Offset
Heating WD curve
Set weather-dependent heating for the additional zone (if [3.4]=1 or 2):