5.4 Setting up the domestic hot water tank
5.4.1 System layout – Integrated DHW tank
A
c
ab
A Domestic hot water
a Cold water IN
b Hot water OUT
c Remote outdoor sensor
5.4.2 Selecting the volume and desired temperature for the DHW tank
People experience water as hot when its temperature is 40°C. Therefore, the DHW
consumption is always expressed as equivalent hot water volume at 40°C.
However, you can set the DHW tank temperature at a higher temperature
(example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water volume at 40°C).
2 Determining the desired temperature for the DHW tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent
hot water volume at 40°C) using typical water volumes:
Question Typical water volume
How many showers are needed per
day?
1shower = 10min×10l/min = 100l
How many baths are needed per day? 1bath = 150l
How much water is needed at the
kitchen sink per day?
1sink = 2min×5l/min = 10l
Are there any other domestic hot water
needs?
Example: If the DHW consumption of a family (4 persons) per day is as follows:
3 showers
1 bath
3 sink volumes
Then the DHW consumption = (3×100l)+(1×150l)+(3×10l)=480l