5 | Application guidelines
Installer reference guide
41
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
5.4.4 DHW pump for instant hot water
Setup
a
c
b
d
A
A Domestic hot water
a Cold water IN
b Domestic hot water OUT (shower (field supply))
c DHW pump (field supply)
d Recirculation connection
By connecting a DHW pump, instant hot water can be available at the tap.
The DHW pump and the installation are field supply and the responsibility of the
installer. For the electrical wiring, see "8.2.5To connect the domestic hot water
pump"[490].
Configuration
For more information, see "10Configuration"[4128].
You can program a schedule to control the DHW pump via the user interface. For
more information, see the user reference guide.
5.4.5 DHW pump for disinfection
Setup
c d e
a
b
A
A Domestic hot water
a Cold water IN
b Domestic hot water OUT (shower (field supply))
c DHW pump (field supply)
d Heater element (field supply)
e Non‑return valve (field supply)
The DHW pump is field-supplied and its installation is the responsibility of the
installer. For the electrical wiring, see "8.2.5To connect the domestic hot water
pump"[490].
If the applicable legislation requires a higher temperature than the maximum
tank setpoint during disinfection (see [2-03] in the field settings table), you can
connect a DHW pump and heater element as shown above.
If applicable legislation requires disinfection of the water piping until the tapping
point, you can connect a DHW pump and heater element (if needed) as shown
above.