5 | Application guidelines
Installer reference guide
46
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
# Power consumption control
1 "5.6.1Permanent power limitation"[446]
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) with one permanent
setting.
Limitation of power in kW or current in A.
2 "5.6.2Power limitation activated by digital inputs"[447]
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) via 4 digital inputs.
Limitation of power in kW or current in A.
3 "5.6.4Current limitation by current sensors"[448]
Allows you to limit the current of the household by limiting the current of
the heat pump system (sum of indoor unit and backup heater).
Limitation of current in A.
4 "5.6.5BBR16 power limitation"[449]
Restriction: Only available in Swedish language.
Allows you to comply with BBR16 regulations (Swedish energy
regulations).
Limitation of power in kW.
Can be combined with the other power consumption controls. If you do
so, the unit uses the most restrictive control.
NOTICE
It is possible to install a field fuse with lower than recommended rating over the heat
pump. For this you must modify field setting [2‑0E] according to the maximum
allowed current over the heat pump.
Note that field setting [2‑0E] overrules all power consumption control settings.
Power limiting the heat pump will reduce performance.
5.6.1 Permanent power limitation
Permanent power limitation is useful to assure a maximum power or current input
of the system. In some countries, legislation limits the maximum power
consumption for space heating and DHW production.
P
i
t
DI
a
b
P
i
Power input
t Time
DI Digital input (power limitation level)
a Power limitation active
b Actual power input
Setup and configuration
No additional equipment needed.