EasyManua.ls Logo

Daikin Altherma 3 GEO Series - Page 190

Daikin Altherma 3 GEO Series
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 | Configuration
Installer reference guide
190
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
[D‑00] Backup heater Compressor
0 Forced OFF Forced OFF
2 Allowed
Power consumption control
Power consumption control
See "5 Application guidelines" [4 24] for detailed information about this
functionality.
# Code Description
[9.9.1] [4-08] Power consumption control:
0 No: Disabled.
1 Continuous: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 Inputs: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
3 Current sensor: Enabled: You can set a
current limitation value (in A) to which the
household current will be limited.
Continuous power consumption control and power consumption control with
digital inputs
The type of limit needs to be set in combination with the continuous power
consumption control and the power consumption control with digital inputs.
# Code Description
[9.9.2] [4-09] Type:
0 Amp: The limitation values are set in A.
1 kW: The limitation values are set in kW.
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
# Code Description
[9.9.3] [5-05] Limit: Only applicable in case of full time
current limitation mode.
0A~50A
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
# Code Description
[9.9.4] [5-05] Limit 1: 0A~50A
[9.9.5] [5-06] Limit 2: 0A~50A
[9.9.6] [5-07] Limit 3: 0A~50A
[9.9.7] [5-08] Limit 4: 0A~50A
Limit when [9.9.1]=Continuous and [9.9.2]=kW:

Table of Contents

Other manuals for Daikin Altherma 3 GEO Series

Related product manuals