EasyManua.ls Logo

Daikin Altherma 3 GEO Series - Page 193

Daikin Altherma 3 GEO Series
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 | Configuration
Installer reference guide
193
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
# Code Description
[9.B.2] [2-0B] Ext. amb. sensor offset: Offset on the
ambient temperature measured on the external
outdoor temperature sensor.
–5°C~5°C, step 0.5°C
Averaging time
The average timer corrects the influence of ambient temperature variations. The
weather-dependent setpoint calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
# Code Description
[9.B.3] [1-0A] Averaging time:
0: No averaging
1: 12hours
2: 24hours
3: 48hours
4: 72hours
Brine low pressure switch
When a brine low pressure switch is installed, the unit must be configured to work
with the switch. When the switch is removed or disconnected, this setting must be
set to OFF.
# Code Description
N/A [C-0B] Activation of the brine low pressure switch
0: OFF
1: On
Bivalent
Alarm output
Alarm output
# Code Description
[9.D] [C–09] Alarm output: Indicates the logic of the alarm
output on the digital I/O PCB during
malfunctioning.
0 Abnormal: The alarm output will be
powered when an alarm occurs. By setting this
value, a distinction is made between the
detection of an alarm, and the detection of a
power failure.
1 Normal: The alarm output will NOT be
powered when an alarm occurs.
See also table below (Alarm output logic).

Table of Contents

Other manuals for Daikin Altherma 3 GEO Series

Related product manuals