5 | Application guidelines
Installer reference guide
33
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Combination: Underfloor heating + Heatpump convectors – Multiple rooms
Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a External room thermostat
b Remote controller of the heatpump convectors
c Remote outdoor sensor
▪ For more information about connecting the electrical wiring to the unit, see
"8.2 Overview of electrical connections for external and internal
actuators"[480].
▪ For each room with heat pump convectors: The heat pump convectors are
directly connected to the indoor unit.
▪ For each room with underfloor heating: Two shut-off valves (field supply) are
installed before the underfloor heating:
- A shut-off valve to prevent hot water supply when the room has no heating
demand
- A shut-off valve to prevent condensation on the floor during cooling operation
of the rooms with heatpump convectors.
▪ For each room with heat pump convectors: The desired room temperature is set
via the remote controller of the heat pump convectors.
▪ For each room with underfloor heating: The desired room temperature is set via
the external room thermostat (wired or wireless).
▪ The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each external room thermostat and
remote controller of the heatpump convectors must be set to match the indoor
unit.
INFORMATION
To increase comfort and performance, we recommend to install the valve kit option
EKVKHPC on each heatpump convector.
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.