EasyManua.ls Logo

Daikin DZ17VSA481AA - Troubleshooting Network and Settings; Network Communication Troubleshooting

Daikin DZ17VSA481AA
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3030
trouBleShootIng
network trouBleShootIng
Communication is achieved by taking the difference between
a positive dc signal and a negative dc signal. The positive dc
signal is termed “data 1” or “1”. Data 1 is positive with respect
to ground (or common). The negative dc signal is termed
“data 2” or “2”. Data 2 is negative with respect to ground (or
common).
Data 1 should be approximately 2.8 volts dc. Data 2 should
be approximately 2.2 volts dc. The voltage difference between
data 1 and data 2 should be approximately 0.6 volts dc.
Verify that the bus DS1 dip switches are in the ON position.
OFF ON
1
TERM
2
This heat pump is a fully communicating system, constituting
a network. Occasionally the need to troubleshoot the network
may arise. The integrated control module has some onboard
tools that can be used to troubleshoot the network. These
tools are: red communications LED, green receive (Rx) LED,
and the learn button.
Red communications LED – Indicates the status of the
network. The table below indicates the LED status and
the corresponding potential problem.
Green receive LED – Indicates network trafc. The table
below indicates the LED status and the corresponding
potential problem.
LEARN button – Used to reset the network. Depress the
button for approximately 5 seconds to reset the network.
Dipswitch Default Factory Settings
Switch # Setting Purpose
OD DS1
1 ON CT Communication Enabled
2 ON CT Communication Enabled
OD DS2
1 OFF
Cooling Emergency Mode for
Future Use*
2 OFF
Cooling Emergency Mode for
Future Use*
*OD DS2 switch 1 and 2 both must be turned off during normal
operation mode
LED COLOR LED Status Indication Probable Causes Corrective Actions
Red Communications LED
(H1P)
Off Nominal condition None None
1 Flash Communications Failure Unknown packet is received Depress learn button
2 Flash Out-of-box reset
Control power up
Learn button depressed
None
Green Receive LED (H2P)
Off
No power
Communications error
No power to Outdoor unit
Open fuse
Communication error
Check circuit breakers and fuses; Replace if needed
Reset network by depressing learn button
Check communication wires (data 1/ data 2 wires);
Replace if needed
1 Steady Flash No network found
Broken/ disconnected communication
wire(s)
Heat pump is installed as a legacy/
traditional system
Check communication wires (data 1/ data 2 wires);
Replace if needed
Check installation type (legacy/ traditional or com-
municating)
Check data 1/ data 2 voltages
Rapid Flashing Nominal network trafc Control is “talking” on network as expected None
On Solid Data 1/Data 2 miss-wire
Data 1 and data 2 wires reversed at indoor
unit, thermostat, or outdoor unit
Short between data 1 and data 2 wires
Short between data 1 or data 2 wires
Check communication wires (data 1/ data 2 wires);
Replace if needed
Check data 1/ data 2 voltages

Table of Contents

Related product manuals