SERVICING
36
Long Radius Street Ell
45°
Street Ell
Short Radius
Street Ell
45°
Ell
Figure 3-1. Oil Trap
SECTION 4. OUTDOOR UNIT IS BELOW THE INDOOR UNIT
1. The maximum elevation (vertical) difference between the outdoor unit and the indoor unit is 90 feet.
2. Suction line must be installed in a manner to prevent liquid migration to the outdoor unit from the
indoor unit.
The heat pump condenser unit is shipped with a predetermined factory charge level as shown in the unit serial plate. For longer line
sets greater than 15 feet, add 0.6 ounces of refrigernat per foot.
NOTICE
T
OTAL
R
EFRIGERANT
=
F
ACTORY
C
HARGE
+ (0.6
OZ
./
FT
. * A
DDITIONAL
F
EET
OF
A
CTUAL
L
INE
S
ET
).
BURYING REFRIGERANT LINES
If burying refrigerant lines can not be avoided, use the following checklist.
1. Insulate liquid and suction lines separately.
2. Enclose all underground portions of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where tubing
enters/exits the enclosure.
3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed.