CTK04 ADDENDUM
95
SET THERMOSTAT TO ADJUST MAXIMUM COMPRESSOR
SPEED
Please follow the following sequence to enter MAXIMUM
compressor speed.
Maximum compressor speed at which the outdoor unit will oper-
ate in cooling or heating mode can be changed using thermostat.
Maximum compressor speed can be changed to get the required
capacity or efficiency. Once the maximum speed is set, the system
operates between the set maximum speed and default low speed.
1. On the HOME screen, select MENU
2. From the MENU screen, select COMFORTNET™ USER MENU.
3. Enter Installer password. (The password is the Date Code
located on the thermostat and is available by entering the
EQUIPMENT STATUS menu and scrolling to the bottom).