Forced Cooling Operation SiBE041102_A
138 Trial Operation and Field Settings
2. Forced Cooling Operation
Indoor Unit
Item Forced Cooling
Conditions The forced cooling operation is allowed when both the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
Command
frequency
58 Hz
End The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
again.
3) Press the ON/OFF button on the remote controller.
Others The protection functions are prior to all others in the forced cooling operation.
ON/OFF
(R14578)
ON/OFF button (SW1)