SiBE041102_A Troubleshooting
Service Diagnosis 55
4.3 Freeze-up Protection Control or Heating Peak-cut
Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated
according to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor
is used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Malfunction
Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C.
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 65°C.
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB

Table of Contents

Other manuals for Daikin FTXN35KEV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTXN35KEV1B and is the answer not in the manual?

Daikin FTXN35KEV1B Specifications

General IconGeneral
BrandDaikin
ModelFTXN35KEV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals