SiBE041102_A Troubleshooting
Service Diagnosis 65
4.10 Compressor Lock
Remote
Controller
Display
E6
Method of
Malfunction
Detection
A compressor lock is detected by the current waveform generated when applying high-
frequency voltage to the motor.
Malfunction
Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Compressor locked
Disconnection of compressor harness
Troubleshooting
Check No.15
Refer to P.91
Turn off the power. Disconnect the
harnesses U, V, and W.
(R14439)
Caution
NO
YES
YES
NO
NO
YES
Check No.15
Check with the inverter checker ().
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
Correct the power supply or
replace the outdoor unit
PCB.
Inverter checker
Part No.: 1225477
Replace the compressor.
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Normal?
Emergency
stop without compressor
running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.

Table of Contents

Other manuals for Daikin FTXN35KEV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTXN35KEV1B and is the answer not in the manual?

Daikin FTXN35KEV1B Specifications

General IconGeneral
BrandDaikin
ModelFTXN35KEV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals