Use the Alarm tab to dene the alarm actions associated with this 
device.  Use the Alarm select tab to select  up to 300 alarm points 
(max 300 per AK-PC controller)
Alarms and Alarm Select
Conguration -> HISTORY
The AK-SM history section allows the collection and recording of 
control parameters, values and status.  The central history 
function allows up to 600 ‘points’ to be congured, a point being 
a temperature, pressure, status, relay, etc.  The collection of 
history allows further analysis using the AK-SM or remote web 
browser, where a graphical representation of this data can be 
made.
To congure history, navigate to the Setup tab (Conguration-
>History).  The following setup lines are visible;
Auto Congure History:  Use this function to auto select typical 
points needed for logging (the AK-SM will select key points in the 
Refrigeration, HVAC, Lighting and Misc control areas.  Manual 
conguration can be done to override these selections or add 
more as required.
Clear History Conguration:  Use this function to clear history 
conguration (points selected for history & the frequency of 
samples)
Clear History log:  Use this function to clear stored history in the 
AK-SM
Start / Suspend History:  Once the relevant points have been 
selected for history collection (using either the Auto history, 
manual or a combination of both) press this line to Start the 
collection.  Press again to Stop collection
Status:  Displays the current status of history collection (Collect-
ing or Suspended)
No of Congured datapoints:  Displays the number of cong-
ured history points (max 600)
Note:  Ensure the correct time & date are set in 
the AK-SM.  Make sure the history collection 
function is running to ensure the collection of 
datapoints.  Use the ‘Start History’ line and 
check that the status reects ‘Collecting’
Auto Congure History
When selecting the auto congure history function 
the AK-SM presents the option to select the history 
collection sample rate.
These can be later changed & modied under the 
relevant history device type (Controllers/Relays/
Sensors/On/O/Variable/Other)
AK-SM 850  User Guide  Lit. no. USCO.PI.R1.E1.02 © Danfoss 07-2013  33