EasyManua.ls Logo

Danfoss AK-SM 850 - Page 47

Danfoss AK-SM 850
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
On/O Tab
The example below shows the Misc On/O tab. Navigate down
the control lines and congure as required.
On/O Tab
Depending on control require-
ments the screen layout may
dier.
Navigate though the options,
adding custom name, AK I/O
address, alarms
Example of On/O Inputs Tab
Name: Enter custom description for Input
Bd-Pt: Enter a valid Board & Point address (using AK I/O modules)
Broadcast:
No: The value of the point will not be broadcast to be used in
logic on other controllers.
Send: The value of the point (whether it is ON or OFF) will be
available on the host network for use by other controllers. Be
sure that each sending Board-Point combination is unique
throughout the system. (If the controller at address #01 is
sending from its Bd-Pt address 1-02, then no other controller
can have an output at its Bd-Pt address 1-02 sending.
Rec: The value of the point is being received from another
controller on the host network. You must enter, in the Bd-Pt
elds, the Bd-Pt address of the sending point.
Type: Select from various option in the drop down list
Voltage: Voltage Input
No Voltage: No Voltage Input
Latching: Latching Input
Closed: Closed Input
Open: Open Input
Number of alarms: Enter the amount of alarms (max 3)
Alarm 1: Enter the alarm level (Disabled, Log only, Normal,
Severe, Critical)
Type: Alarm if above or if below limit (seen below)
Limit: Enter the alarm limit
Delay: Enter delay time
Units: Seconds, Minutes, Hours
From: Denes alarm output time window
To: Denes alarm output time window
Days: Dene the days associated with alarm
Action: Dene the alarm action
AK-SM 850 User Guide Lit. no. USCO.PI.R1.E1.02 © Danfoss 07-2013 47

Related product manuals