8-31 Address
Range: Function:
1
*
[1 - 126 ] Enter the address for the FC (standard) port.
Valid range: 1 - 126.
8-32 FC Port Baud Rate
Option: Function:
[0] 2400 Baud
[1] 4800 Baud
[2]
*
9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[7] 115200 Baud Baud rate selection for the FC (standard) port.
8-35 Minimum Response Delay
Range: Function:
10ms
*
[1 - 500 ms] Specify the minimum delay time between receiving a request
and transmitting a response. This is used for overcoming mo-
dem turnaround delays.
8-36 Max Response DelayMax Response Delay
Range: Function:
5000ms
*
[1 - 10000 ms] Specify the maximum permissible delay time between transmit-
ting a request and receiving a response. Exceeding this delay
time will cause control word time-out.
8-37 Max Inter-Char Delay
Range: Function:
25ms
*
[0 - 30 ms] Specify the maximum permissible time interval between receipt
of two bytes. This parameter activates time-out if transmission
is interrupted.
This parameter is active only when par. 8-30 is set to
FC MC
[1]
protocol.
8-40 FC MC Protocol Set
Option: Function:
[1]
*
Standard Telegram 1
[200] Custom Telegram Enables use of freely configurable telegrams or standard tele-
grams for the FC port.
2.11.5. 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus merging.
FC 300 Programming Guide 2. How to Programme
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark