[1] On Enables reference via the fieldbus.
10-15 Net Control
Read only from LCP.
Select the control source in Instance 21/71 and 20-70.
[0]
*
Off Enables control via analog/digital inputs.
[1] On enable control via the fieldbus.
2.13.4. 10-2* COS Filters
Parameters for configuring COS filter settings.
10-20 COS Filter 1
Range: Function:
0000
*
[0 - FFFF] Enter the value for COS Filter 1 to set up the filter mask for the
Status Word. When operating in COS (Change-Of-State), this
function filters out bits in the Status Word that should not be
sent if they change.
10-21 COS Filter 2
Range: Function:
0000
*
[0 - FFFF] Enter the value for COS Filter 2, to set up the filter mask for the
Main Actual Value. When operating in COS (Change-Of-State),
this function filters out bits in the Main Actual Value that should
not be sent if they change.
10-22 COS Filter 3
Range: Function:
0000
*
[0 - FFFF] Enter the value for COS Filter 3, to set up the filter mask for PCD
3. When operating in COS (Change-Of-State), this function fil-
ters out bits in PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range: Function:
0000
*
[0 - FFFF] Enter the value for COS Filter 4 to set up the filter mask for PCD
4. When operating in COS (Change-Of-State), this function fil-
ters out bits in PCD 4 that should not be sent if they change.
2.13.5. 10-3* Parameter Access
Parameter group providing access to indexed parameters and defining programming set-up.