0-41 [Off] Key on LCP
Option: Function:
[0] Disabled Avoids accidental stop of the frequency converter.
[1]
*
Enabled
[2] Password Avoids unauthorised stop. If par. 0-41 is included in the Quick
Menu, then define the password in par. 0-65
Quick Menu Pass-
word
.
0-42 [Auto on] Key on LCP
Option: Function:
[0] Disabled avoid accidental start of the frequency converter in Auto mode.
[1]
*
Enabled
[2] Password Avoids unauthorised start in Auto mode. If par. 0-42 is included
in the Quick Menu, then define the password in par. 0-65
Quick
Menu Password
.
0-43 [Reset] Key on LCP
Option: Function:
[0] Disabled Avoids accidental alarm reset.
[1]
*
Enabled
[2] Password Avoids unauthorised resetting. If par. 0-43 is included in the
Quick Menu, then define the password in par. 0-65
Quick Menu
Password
.
2.3.7. 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the LCP.
0-50 LCP Copy
Option: Function:
[0]
*
No copy
[1] All to LCP Copies all parameters in all set-ups from the frequency convert-
er memory to the LCP memory.
[2] All from LCP Copies all parameters in all set-ups from the LCP memory to the
frequency converter memory.
[3] Size indep. from LCP copy only the parameters that are independent of the motor
size. The latter selection can be used to programme several
drives with the same function without disturbing motor data.
[4] File from MCO to LCP
[5] File from LCP to MCO
This parameter cannot be adjusted while the motor is running.
2. How to Programme FC 300 Programming Guide
40
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark