26 of 114
M-AP-001-EN Rev. Q
3.4.3 Bearing Motor Compressor Controller
The hardware and software for the compressor controller and the bearing/motor controller physically
reside in the BMCC. The BMCC is the central processor of the compressor.
3.4.4 Compressor Control
The Compressor Controller is continuously updated with critical data from external sensors that
indicate the compressor’s operating status. Under program control, the compressor controller can
respond to changing conditions and requirements to ensure optimum system performance.
3.4.5 Capacity Control
One of the Compressor Controller’s primary functions is to control the compressor’s motor speed and
IGV position in order to satisfy load requirements and to avoid surge and choke conditions. However,
the majority of capacity control can be achieved via motor speed.
3.4.6 Expansion Valve Control
The onboard Electronic Expansion Valve (EXV) driver uses manual control only. Depending on the
application, a load balancing (hot gas bypass) valve can be manually driven by the auxiliary EXV
output. Load balancing allows the compressor to obtain lower capacities at higher pressure ratios. The
valve opens to lower the overall pressure ratio and thereby reduces the lift, enabling the compressor
to reduce speed/unload.
3.4.7 Motor/Bearing Control
The magnetic bearing system physically supports a rotating shaft while enabling non-contact
between the shaft and surrounding stationary surfaces. A digital bearing controller and motor
controller provide the PWM command signals to the Bearing PWM Amplifier and Inverter, respectively.
The bearing controller also collects shaft position inputs from sensors and uses the feedback to
calculate and maintain the desired shaft position.
3.4.8 Monitoring Functions
The compressor controller monitors more than 60 parameters, including:
Gas pressure and temperature monitoring
Line voltage monitoring and phase failure detection
Motor temperature
Line currents
External interlock
3.4.9 Abnormal Conditions
The compressor controller responds to abnormal conditions by monitoring:
Surge RPMs
Choke RPMs
Power failure/phase unbalance
Low/high ambient temperature
High discharge pressure
Low suction pressure
Motor-cooling circuit failure (over temperature)
Refrigerant loss
Power supply
Overcurrent
3.4.10 Bearing PWM Amplifier
The Bearing PWM Amplifier supplies current to the radial and axial magnetic bearing actuators.
The PWM Amplifier consists of high-voltage switches that are turned on and off at a high frequency,
as commanded by the PWM signal from the BMCC.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor Twin-Turbine TTS Series and is the answer not in the manual?

Danfoss Turbocor Twin-Turbine TTS Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor Twin-Turbine TTS Series
CategoryAir Compressor
LanguageEnglish

Related product manuals