Setup msb Setup lsb Function
0 0 Setup 1
0 1 Setup 2
1 0 Setup 3
1 1 Setup 4
Table 4.38 Function Description for [0] Digital input
Setup msb Setup lsb Function
0 0 Setup 1
0 1 Setup 2
1 0 Setup 3
1 1 Setup 4
Table 4.39 Function Description for [1] Serial communication
Bus Setup
msb
Bus Setup
lsb
Dig. Setup
msb
Dig. Setup
lsb
Setup no.
0 0 0 0 1
0 0 0 1 1
0 0 1 0 1
0 0 1 1 1
0 1 0 0 1
0 1 0 1 2
0 1 1 0 1
0 1 1 1 2
1 0 0 0 1
1 0 0 1 1
1 0 1 0 3
1 0 1 1 3
1 1 0 0 1
1 1 0 1 2
1 1 1 0 3
1 1 1 1 4
Table 4.40 Function Description for [2] Logic and
Bus Setup
msb
Bus Setup
lsb
Dig. Setup
msb
Dig. Setup
lsb
Setup no.
0 0 0 0 1
0 0 0 1 2
0 0 1 0 3
0 0 1 1 4
0 1 0 0 2
0 1 0 1 2
0 1 1 0 4
0 1 1 1 4
1 0 0 0 3
1 0 0 1 4
1 0 1 0 3
1 0 1 1 4
1 1 0 0 4
1 1 0 1 4
1 1 1 0 4
1 1 1 1 4
Table 4.41 Function Description for [3] Logic or
508
Selection of preset ref.
Value:
Digital input (DIGITAL INPUT) [0]
Serial comunication (SERIAL PORT) [1]
Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See function description of parameter 502 Coasting stop.
Description of choice:
Preset references via serial communication are active when
parameter 512 Telegram profile is set to [1] FC protocol.
509
Bus jog 1 (BUS JOG 1 FREQ.)
510 Bus jog 2 (BUS JOG 2 FREQ.)
Value:
0.0 - parameter 202 Output frequency high
limit
10,0 Hz
Function:
If parameter 512 Telegram Profile shows the selection [0]
Profidrive, 2 fixed speeds (Jog 1 or Jog 2) can be selected
via the serial port.
The function is the same as in parameter 213 Jog frequency.
Description of choice:
Jog frequency f
JOG
can be selected between 0 Hz and f
MAX
.
512
Telegram Profile
Value:
Profidrive (Profidrive) [0]
FC protocol (FC protocol) [1]
Function:
It is possible to select between 2 different control word
profiles.
Programming
Design Guide
MG27E402 Danfoss A/S © Rev. May/2014 All rights reserved. 119