EasyManuals Logo
Home>Danfoss>DC Drives>VLT 2800

Danfoss VLT 2800 Design Guide

Danfoss VLT 2800
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
4.1.1 Setup Shift
Selection of Setup via terminals 29 and 33.
Parameter 305 Digital input=[31] Selection of Setup,
lsb
Parameter 307 Digital input=[32] Selection of Setup,
msb
Parameter 004 Active setup=[5] Multi Setup
Illustration 4.1 Setup Selection
004 Active Set-up
Value:
Factory Set-up (FACTORY SET-UP) [0]
Set-up 1 (setup 1) [1]
Set-up 2 (setup 2) [2]
Set-up 3 (setup 3) [3]
Set-up 4 (setup 4) [4]
Multi Setup (MULTI SET-UP) [5]
Function:
The active parameter set-up is selected here. All
parameters can be programmed in 4 individual parameter
set-ups. Use this parameter to shift between set-ups via a
digital input or via serial communication.
Description of choice:
[0] Factory Set-up contains the factory-set parameter values.
Set-up 1-4 [1]-[4] are 4 individual set-ups which can be
selected as required. [5] Multi Set-up is used where remote-
controlled shifts between the 4 set-ups via a digital input
or via serial communication is required.
005
Programming Setup
Value:
Factory Setup (FACTORY SETUP) [0]
Setup 1 (setup 1) [1]
Setup 2 (setup 2) [2]
Setup 3 (setup 3) [3]
Setup 4 (setup 4) [4]
Active Setup (ACTIVE SETUP) [5]
Function:
Select which set-up to programme during operation
(applies both via the control panel and the serial
communication port). It is, for example, possible to
programme [2] Setup 2 , while the active set-up is set to [1]
Setup 1 in parameter 004 Active Setup.
Description of choice:
[0] Factory Setup contains the factory-set data and can be
used as a source of data if the other set-ups are to be
reset to a known status. Setup 1-4 [1]-[4] are individual set-
ups that can be programmed freely during operation. If [5]
Active Setup is selected, the programming set-up is equal
to parameter 004 Active Setup.
NOTICE
If data is modified or copied to the active set-up, the
modifications have an immediate effect on the unit's
operation.
006 Setup Copying
Value:
No copying (NO COPY) [0]
Copy to Setup 1 from #
(COPY TO SETUP 1) [1]
Copy to Setup 2 from #
(COPY TO SETUP 2) [2]
Copy to Setup 3 from #
(COPY TO SETUP 3) [3]
Copy to Setup 4 from #
(COPY TO SETUP 4) [4]
Copy to all Setups from # (copy to all) [5]
Function:
Copy from the selected active set-up in parameter 005
Programming set-up to the selected set-up or set-ups in
this parameter.
Description of choice:
Copying begins when the required copying function has
been selected and the [OK]/[CHANGE DATA] key has been
pressed. The display indicates when copying is in progress.
NOTICE
Copying is only possible in Stop (motor stopped in
connection with a stop command).
007 LCP Copy
Value:
No copying (NO COPY) [0]
Upload all parameters (UPL. ALL PAR.) [1]
Download all parameters (DWNL. ALL PAR.) [2]
Download size-independent parameters
(DWNL.OUTPIND.PAR.) [3]
Function:
Use parameter 007 LCP copy to use the LCP 2 control
panel's integral copy function. Use the function to copy all
parameter set-ups from one frequency converter to
another by moving the LCP 2 control panel.
Description of choice:
Select [1] Upload all parameters to transfer all parameter
values to the control panel. Select [2] Download all
parameters if all parameter values transferred are to be
Programming
Design Guide
62 Danfoss A/S © Rev. May/2014 All rights reserved. MG27E402
44

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals