Operating
mode
Description
O
The drive does not react to any control signal until [Auto On] or [Hand On] is pressed.
9.2.3 Status Messages - Reference Site
Table 94: Reference Site
Reference site
Description
Remote
The speed reference is given from:
External signals.
Serial communication.
Internal preset references.
Local
The drive uses reference values from the LCP.
9.2.4 Status Messages - Operation Status
Table 95: Operation Status
Operation
status
Description
AC brake
AC brake was selected in parameter 2-10 Brake Function. The AC brake overmagnetizes the motor to achieve a con-
trolled slow down.
AMA nish
OK
Automatic motor adaptation (AMA) was carried out successfully.
AMA ready
AMA is ready to start. To start, press [Hand On].
AMA run-
ning
AMA process is in progress.
Braking
The brake chopper is in operation. The brake resistor absorbs the generative energy.
Braking
max.
The brake chopper is in operation. The power limit for the brake resistor dened in parameter 2-12 Brake Power
Limit (kW) has been reached.
Coast
[2] Coast inverse was selected as a function for a digital input (parameter group 5–1* Digital Inputs). The corre-
sponding terminal is not connected.
Coast activated by serial communication.
No output from the drive to the motor.
Ctrl. ramp-
down
[1] Ctrl. ramp-down was selected in parameter 14-10 Mains Failure.
The mains voltage is below the value set in parameter 14-11 Mains Voltage at Mains Fault.
The drive ramps down the motor in a controlled manner.
Current
high
The drive output current is above the limit set in parameter 4-51 Warning Current High.
Current low
The drive output current is below the limit set in parameter 4-52 Warning Speed Low.
DC hold
DC hold is selected in parameter 1-80 Function at Stop and a stop command is active. The motor is held by a DC
current set in parameter 2-00 DC Hold Current.
DC stop
The motor is held with a DC current (parameter 2-01 DC Brake Current) for a specied time (parameter 2-02 DC Brak-
ing Time).
AQ262141056213en-000201 / 130R0882120 | Danfoss A/S © 2020.09