10.8.2 Contactor Switches
The mains contactor is an option. All units ordered and supplied with a factory-installed contactor require a Class L/J branch circuit
fusing to meet the 65 kA SCCR for the drive system.
This option makes it possible to connect or disconnect the drive from the mains by using a control switch on the control compart-
ment door or an external switch. The external switch must be wired to terminals XD0. See 5.3 Wiring Overview for D9h and D10h
Enclosed Drives and 5.4 Wiring Overview for E5h and E6h Enclosed Drives. The mains contactor is supplied with 2 sets of auxiliary
switches (1 normally open and 1 normally closed). These switches are on the sides of the contactor. By default, the NO auxiliary
switch is wired at the factory and used by the system.
Rated operation current @ 230 V
6 A
Rated operation current @ 380 V
4 A
Rated operation current @ 480 V
1.5 A
Conventional thermal current, Ith
10 A
Rated voltage
500 V AC
Rated impulse withstand voltage
600 V AC
Table 115: Mains Contactor Switches for N110–N315 Models, 380–480 V
N110
N132
N160
N200
N250
N315
IEC
185 A/1000 V
185 A/1000 V
185 A/1000 V
400 A/1000 V
580 A/1000 V
500 A/1000 V
Eaton P/N
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE500M22A
UL
185 A/1000 V
185 A/1000 V
185 A/1000 V
400 A/1000 V
400 A/1000 V
580 A/1000 V
Eaton P/N
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE580N22A
XTCE580N22A
Table 116: Mains Contactor Switches for N355–N560 Models, 380–480 V
N355
N400
N450
N500
N560
IEC
580 A/1000 V
580 A/1000 V
580 A/1000 V
820 A/1000 V
820 A/1000 V
Eaton P/N
XTCE580N22A
XTCE580N22A
XTCE580N22A
XTCE820N22A
XTCE820N22A
UL
820 A/1000 V
820 A/1000 V
820 A/1000 V
1000 A/1000 V
1000 A/1000 V
Eaton P/N
XTCE820N22A
XTCE820N22A
XTCE820N22A
XTCEC10N22A
XTCEC10N22A
Table 117: Mains Contactor Switches for N110–N315 Models, 525–690 V
N110
N132
N160
N200
N250
N315
IEC
185 A/1000 V
185 A/1000 V
185 A/1000 V
400 A/1000 V
400 A/1000 V
400 A/1000 V
Eaton P/N
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
UL
185 A/1000 V
185 A/1000 V
185 A/1000 V
400 A/1000 V
400 A/1000 V
400 A/1000 V
Eaton P/N
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
XTCE400M22A
Table 118: Mains Contactor Switches for N400–N630 Models, 525–690 V
N400
N450
N500
N560
N630
IEC
400 A/1000 V
580 A/1000 V
580 A/1000 V
580 A/1000 V
580 A/1000 V
AQ262141056213en-000201 / 130R0882162 | Danfoss A/S © 2020.09