When supplied from an isolated mains source (IT mains or oating delta) or TT/TN-S mains with a grounded leg (grounded
delta), ensure that parameter 14-50 RFI Filter is set to [0] O to avoid damage to the DC link and to reduce ground capacity
currents.
Tighten the terminals in accordance with the specications shown in 10.11 Fastener Torque Ratings.
Example
e30bu172.10
1
2
4
3
Illustration 48: Connection Points for Mains to Input Power Option (Enclosed Drive Congured Without Power Options Cabinet)
Lower cover
Input power terminals (contactor option is shown)
DC terminals
Grounding bar
AQ262141056213en-000201 / 130R0882 | 83Danfoss A/S © 2020.09
Electrical Installation
VLT® AQUA Drive FC 202
Operating Guide

Table of Contents