11.2 International/North American Default Parameter Settings
Setting parameter 0-03 Regional Settings to [0] International or [1] North America changes the default settings for some
parameters. Table 11.2 lists those parameters that are aected.
Parameter International default parameter value North American default parameter value
Parameter 0-03 Regional Settings International North America
Parameter 0-71 Date Format DD-MM-YYYY MM/DD/YYYY
Parameter 0-72 Time Format 24 h 12 h
Parameter 1-20 Motor Power [kW]
1) 1)
Parameter 1-21 Motor Power [HP]
2) 2)
Parameter 1-22 Motor Voltage 230 V/400 V/575 V 208 V/460 V/575 V
Parameter 1-23 Motor Frequency 50 Hz 60 Hz
Parameter 3-03 Maximum Reference 50 Hz 60 Hz
Parameter 3-04 Reference Function Sum External/Preset
Parameter 4-13 Motor Speed High Limit
[RPM]
3)
1500 RPM 1800 RPM
Parameter 4-14 Motor Speed High Limit [Hz]
4)
50 Hz 60 Hz
Parameter 4-19 Max Output Frequency 100 Hz 120 Hz
Parameter 4-53 Warning Speed High 1500 RPM 1800 RPM
Parameter 5-12 Terminal 27 Digital Input Coast inverse External interlock
Parameter 5-40 Function Relay Alarm No alarm
Parameter 6-15 Terminal 53 High Ref./Feedb.
Value
50 60
Parameter 6-50 Terminal 42 Output Speed 0-HighLim Speed 4-20 mA
Parameter 14-20 Reset Mode Manual reset Innite auto reset
Parameter 22-85 Speed at Design Point
[RPM]
3)
1500 RPM 1800 RPM
Parameter 22-86 Speed at Design Point [Hz] 50 Hz 60 Hz
Parameter 24-04 Fire Mode Max Reference 50 Hz 60 Hz
Table 11.2 International/North American Default Parameter Settings
1) Parameter 1-20 Motor Power [kW] is only visible when parameter 0-03 Regional Settings is set to [0] International.
2) Parameter 1-21 Motor Power [HP] is only visible when parameter 0-03 Regional Settings is set to [1] North America.
3) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [0] RPM.
4) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [1] Hz.
11.3
Parameter Menu Structure
Appendix Operating Guide
MG21A502 Danfoss A/S © 09/2018 All rights reserved. 149
11 11