Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
130BB934.11
Function Setting
Parameter 5-10
Terminal 18
Digital Input
[8] Start
Parameter 5-11
Terminal 19
Digital Input
[10] Reversing*
Parameter 5-12
Terminal 27
Digital Input
[0] No
operation
Parameter 5-14
Terminal 32
Digital Input
[16] Preset ref
bit 0
Parameter 5-15
Terminal 33
Digital Input
[17] Preset ref
bit 1
Parameter 3-10
Preset Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
*=Default value
Notes/comments:
Table 8.7 Wiring Conguration for Start/Stop with Reversing
and 4 Preset Speeds
8.4
Wiring Congurations for an External
Alarm Reset
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB928.11
Function Setting
Parameter 5-11
Terminal 19
Digital Input
[1] Reset
*=Default value
Notes/comments:
Table 8.8 Wiring Conguration for an External Alarm Reset
Wiring Conguration Exampl... Operating Guide
MG21A502 Danfoss A/S © 09/2018 All rights reserved. 75
8 8

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals