FC 300 Design Guide
How to Program
Display Contrast Adjustment
Press [status] and [
] for darker display
Press [status] and [
]forbrighterdisplay
LEDs:
Green LED/On: Indicates if control section is working.
Yellow LED/Warn.: Indicates a warning.
Flashing Red LED/Alarm: Indicates an alarm.
Most FC 300 parameter set-ups can be changed immediately via the control panel, unless a p assword
has been created via par. 0-60 Main Menu Password or via par. 0-65 Quick Menu Password.
LCP keys
[Status] indicates the status of the adjustable frequency drive or the motor. You can choose
between 3 different readouts by pr essing the [Status] key:
5-line readouts, 4-line readouts or Smart Logic Control.
[Quick Menu] allows quick access to different Quick Menus such as:
- My Personal Menu
- Quick Set-up
- Changes Made
- Loggings
[Main Menu] is used for programming all parameters.
[Alarm Log] displays an Alar m list of the five latest alarms (numbered A1-A5). To obtain add itional details
about an alarm, use the arrow keys to maneuver to the
alarm number and press [OK]. Information about the
condition of the adjustable freque ncy drive right bef ore entering the alarm mode will be provided.
[Back] reverts to the previous step or layer in the navigation structure.
[Cancel] records the last change or command as long as the display has not been changed.
[Info] supplies information about a command, parameter, or function in any display window.
Exit info mode by pressing either [Info], [Back], or [Cancel].
[OK] is used for choosing a parameter marked b y the cursor and for enabling the change of a parameter.
[Hand on] e n able s control of the adjustable frequency drive via the LCP. [Hand on] also starts the
motor, and it is now p ossible to ent
er the motor speed data by means of the arrow keys. The key can
be selected as Ena ble [1] or Disable [0] via par. 0-40 [Hand on] ke y on LCP.
External stop signals activated by means of control signals or a serial bus will override
a “start command given v ia th
eLCP.
[Off] is used for stopping the
connected motor. The key can be selected as Enable
[1] or Disable [0] v ia pa r. 0-41 [Off] key on LCP.
[Auto On] is us ed if the adjusta ble frequency drive is to be controlle d via the control terminals
and/or serial communication. When a start signal is applied on the control terminals and/or
the bus, the adjustable
frequency drive will start. The key can be selected as Enable [1]
or Disa ble [0] via par. 0-42 [Auto on] Key on LCP.
120
MG.33.B3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals