Table 49: Recommended Maximum UL Fuse Class, Voltage Range 525–690 V, Enclosure Sizes A, B, and C
1
Bussmann Class T allowed up to 6 A.
Table 50: External (Customer Supplied) Branch Circuit Protection
Maximum in-
terrupting
rating for lis-
ted circuit
breakers
0.37 (0.5), 0.55
(0.75), 0.75 (1),
1.1 (1.5), 2.2 (3),
3.0 (4), 4.0 (5), 5.5
(7.5), 7.5 (10)
Any UL 489 listed circuit breaker maxi-
mum 25 A.
ABB MS165–25 480 V/277 Y 65 kA
ABB MS165–25 480 V/277 Y 65 kA
4.0 (5), 5.5 (7.5),
7.5 (10)
ABB MS165–25 600 V/347 Y 30 kA
ABB MS165–54 480 V/277 Y 65 kA
11.0 (15), 15.0
(20), 18.0 (25)
ABB MS165–54 480 V/277 Y 65 kA