2.4.5.1 AC Line Input Connection for A2
and A3
1. Mount the two screws on the mounting plate
2. Slide the mounting plate into place and tighten
fully
-DC+DC
BR- BR+ U V W
99
M A I N S
95
RELAY 1 RELAY 2
- LC +
130BA261.10
Figure 2.20 Mounting Plate Position
3. Mount and tighten ground cable
130BA262.10
M
I N S
+DC
BR-
BR+
U
V
W
RELAY 1 RELAY 2
95
Figure 2.21 Ground Cable Mounting
WARNING
The ground connection cable cross-section must be at
least 0.016 in
2
[10 mm
2
] or two rated line power wires
terminated separately according to EN 50178/IEC
61800-5-1.
Installation Instruction Manual
20 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG16E222