Digital Inputs/Outputs
Terminal Parameter Default
Setting
Description
55 -
Common for analog
input.
Serial Communication
61 -
Integrated RC filter for
cable screen. ONLY for
connecting the shield
when experiencing
EMC problems.
68 (+) 8-3* RS-485 Interface. A
control card switch is
provided for
termination resistance.
69 (-) 8-3*
Relays
01, 02, 03 5-40 [2] Drive ready Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.
04, 05, 06 5-40 [5] Running
Table 2.5 Terminal Description
2.4.6.2
Wiring to Control Terminals
Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in Figure 2.29.
Figure 2.29 Unplugging Control Terminals
1. Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Figure 2.30.
2. Insert the bared control wire into the contact.
3. Remove the screwdriver to fasten the control wire
into the contact.
4. Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
See chapter 10.1 Power-dependent Specifications for control
terminal wiring sizes.
See chapter 6 Application Set-up Examples for typical control
wiring connections.
2
1
10 mm
130BA310.10
12 13
18
19
27
29
32
33
Figure 2.30 Connecting Control Wiring
2.4.6.3
Using Shielded Control Cables
Correct shielding
The preferred method in most cases is to secure control
and serial communication cables with shielding clamps
provided at both ends to ensure best possible high
frequency cable contact.
If the ground potential between the adjustable frequency
drive and the PLC is different, electrical noise may occur
that will disturb the entire system. Solve this problem by
fitting an equalizing cable next to the control cable.
Minimum cable cross-section: 16 mm
2
.
1
2
PE
FC
PE
PLC
130BB922.12
PE PE
<10 mm
Figure 2.31 Correct Shielding
1
Min. 0.025 in
2
[16 mm
2
]
2 Equalizing cable
Table 2.6 Legend to Figure 2.31
Installation
Instruction Manual
24 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG16E222
22