Adjustable frequency drive
Typical Shaft Output [kW]
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
P18K
18.5
P22K
22
P30K
30
P37K
37
P45K
45
IP20/Chassis
7)
B3 B3 B3 B4 B4 C3 C3 C4 C4
IP21/NEMA 1 B1 B1 B1 B2 C1 C1 C1 C2 C2
IP55/Type 12 B1 B1 B1 B2 C1 C1 C1 C2 C2
IP66/NEMA 4X B1 B1 B1 B2 C1 C1 C1 C2 C2
Typical Shaft Output [HP]
at 208 V
7.5 10 15 20 25 30 40 50 60
Output current
Continuous
(3x200–240 V) [A]
24.2 30.8 46.2 59.4 74.8 88.0 115 143 170
Intermittent
(3x200–240 V) [A]
26.6 33.9 50.8 65.3 82.3 96.8 127 157 187
Continuous
kVA (208 V AC) [kVA]
8.7 11.1 16.6 21.4 26.9 31.7 41.4 51.5 61.2
Max. input current
Continuous
(3x200–240 V) [A]
22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0
Intermittent
(3x200–240 V) [A]
24.2 30.8 46.2 59.4 74.8 88.0 114.0 143.0 169.0
Additional Specifications
Estimated power loss at rated max.
load [W]
4)
269 310 447 602 737 845 1140 1353 1636
IP20 max. cable cross-section (line
power, brake, motor and load
sharing)
10, 10 (8,8,-) 35,-,-(2,-,-) 35 (2) 50 (1) 300 MCM (150)
IP21, IP55, IP66 max. cable cross-
section (line power, motor)
[mm
2
/(AWG)]
10, 10 (8,8,-)
35, 25, 25
(2, 4, 4)
50 (1) 300 MCM (150)
IP21, IP55, IP66 max. cable cross-
section (brake, load sharing)
[mm
2
/(AWG)]
16, 10, 16 (6, 8, 6) 35,-,-(2,-,-) 50 (1) 95 (3/0)
With line power disconnect switch
included:
16/6 35/2 35/2 70/3/0
185/
kcmil350
Weight enclosure IP20 (lb [kg]) 26.46 [12] 26.46 [12] 26.46 [12]
51.81
[23.5]
51.81
[23.5]
77.16 [35] 77.16 [35]
110.23
[50]
110.23
[50]
Weight enclosure IP21 (lb [kg]) 50.71 [23] 50.71 [23] 50.71 [23] 59.53 [27] 99.21 [45] 99.21 [45] 99.21 [45] 143.3 [65] 143.3 [65]
Weight enclosure IP55 (lb [kg]) 50.71 [23] 50.71 [23] 50.71 [23] 59.53 [27] 99.21 [45] 99.21 [45] 99.21 [45] 143.3 [65] 143.3 [65]
Weight enclosure IP66 (lb [kg]) 50.71 [23] 50.71 [23] 50.71 [23] 59.53 [27] 99.21 [45] 99.21 [45] 99.21 [45] 143.3 [65] 143.3 [65]
Efficiency
3)
0.96 0.96 0.96 0.96 0.96 0.97 0.97 0.97 0.97
Table 10.2 Line Power Supply 3x200–240 V AC - Normal overload 110% for 1 minute
Specifications Instruction Manual
MG16E222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 77
10 10

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals