EasyManuals Logo

Danfoss VLT FC 103 Instruction Manual

Danfoss VLT FC 103
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature
reaches a predefined level. An overload temperature cannot be reset until the temperature of the heatsink is
below the values stated in the tables on the following pages (guideline - these temperatures may vary for different
power sizes, frame sizes, enclosure ratings, etc.).
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
The adjustable frequency drive constantly checks for critical levels of internal temperature, load current, high
voltage on the intermediate circuit and low motor speeds. As a response to a critical level, the adjustable
frequency drive can adjust the switching frequency and/or change the switching pattern in order to ensure the
performance of the adjustable frequency drive.
Specifications Instruction Manual
90 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG16E222
1010

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals