EasyManua.ls Logo

Danfoss VLT HVAC

Danfoss VLT HVAC
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Use a clamp from the accessory bag to connect the screen to
the frequency converter decoupling plate for control cables.
See section entitled
Earthing of Screened/Armoured Control Cables
for
the correct termination of control cables.
130BA681.10
130BA681.10
5.2.13 Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used to select a current (0-20
mA) or a voltage (0 to 10 V) configuration of the analog input terminals
53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination on the RS-485
port (terminals 68 and 69).
See drawing
Diagram showing all electrical terminals
in section
Electrical
Installation.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
NB!
It is recommended to only change switch position at power off.
5 How to Install VLT
®
HVAC Drive Design Guide
104
MG.11.B9.02 - VLT
®
is a registered Danfoss trademark
5

Table of Contents

Other manuals for Danfoss VLT HVAC

Related product manuals