DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 41 -
ICON and No:
DESCRIPTION
ADJUSTMENT LIMITS
Factory
Set
E.01
PRESS. CONTROL :
Pressure sensor type
0: Analog sensor connected
1: Pressure switch connected
If this parameter is set to 1 then parameters
E.02 ... E.06 will not be visible.
0
E.02
PRESS.TOP RANGE :
Pressure upper display
limit
1.7... 99.9
15.0 bar
E.03
HIGH PRES.ALARM :
High pressure alarm limit
(E.02-0.5) ... (E.04+0.2)
8.5 bar
E.04
STOP PRESSURE :
(E.03-0.2) ... (E.05+0.2)
7.4 bar
E.05
START PRESSURE :
0.5 ... (E.04-0.2)
6.5 bar
E.06
PRES.SNSR.OFSET :
Pressure sensor offset
adjustment
-2.0 ... +2.0
0.0 bar
E.07
TEMP. TOP RANGE :
Temperature display
upper limit
(E.08+2) ... 130
130 °C
E.08
HIGH TEMP.ALARM :
High outlet temperature
alarm limit
(E.09+2) ... (E.07-2)
108 °C
E.09
HIGH TEMP.WARNG :
High outlet temperature
warning limit
(E.10+2) ... (E.08-2)
103 °C
E.10
LOW TEMP. ALARM :
Low outlet temperature
alarm limit
-10 ... (E.09-2)
0 °C
E.11
TEMP. OFFSET :
Temperature sensor
offset adjustment
-10 ... +10
0 °C
10.2.5. COMPRESSOR PARAMETERS