DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 42 -
ICON and No:
DESCRIPTION
ADJUSTMENT LIMITS
Factory
Set
E.12
MOTOR PTC :
Motor PTC connection
0: Not connected
1: Connected
If this sensor type is selected, when the sensor
impedance is over 2000 ohms, the ALARM 09
Motor PTC High Temperature will occur.
0
E.13
AUTO. RESTART :
Automatic restart
0: No (controller turns on at STOP
mode)
1: Yes (controller turns on at the last
mode)
2: Automatic restart (PORO)
0
E.14
CMPNS.PRES.TEMP. :
Pressure compensation
temperature
0 ... (E.09)
Until outlet air temperature reaches this level,
instead of E.04 Stop Pressure, E.05+(E.04-
E.05)/4 will be used.
Thus the compressor will stop before reaching
the stop pressure.
0 °C
E.15
DELAY BETWN.REL :
Delay between relays
20 ... 250 ms
This is the minimum period between release of
a relay and operation of another relay.
100 ms
E.16
TEMP.-2 SENSOR :
Temperature sensor 2
operation type
0: Not connected
1: Reads absolute temperature
2: Reads differential temperature
If this parameter is set to 0 then parameters
E.17, E.18, E.19, E.20 and E.21 will not be
visible.
0
E.17
TEMP.-2 TOP :
Temperature 2 display
upper limit
(E.18+2) ... 200
130 °C
E.18
TEMP-2 HGH ALRM :
High temperature 2
alarm limit (differential
temperature alarm limit)
(E.19+2) ... (E.17-2)
(Differential alarm limit)
110 °C
E.19
TEMP-2 LOW ALRM
Low temperature 2
alarm limit (differential
temperature warning
limit)
-40 ... (E.18-2)
(differential warning limit)
-10 °C