DK-45 Kullanım Kılavuzu V1.0 (22.09.2016)
- 43 -
ICON and No:
DESCRIPTION
ADJUSTMENT LIMITS
Factory
Set
E.20
T2 AL WRN TIME :
Temperature 2
alarm/warning automatic
reset delay
1 ... 600
10 sec
E.21
TEMP.-2 OFFSET :
Temperature sensor 2
offset adjustment
-10 ... +10
0 °C
E.22
STAR TIMER :
Star relay timer
2 ... 20
7 sec
E.23
STAR DELTA TIME :
Star / delta transition
timer
10 ... 50
15 ms
E.24
TIME BEFOR.LOAD :
Time before load
1 ... 999 Sec
2 sec
E.25
UNLOAD TIME :
0 ... 10
2 minute
E.26
VAR.UNLOAD TIME :
Variable unload timer
enable
0: Constant unload timer
1: Variable unload timer
Please see chapter 6.8 for details.
0
E.27
SAFETY TIMER :
Safety delay timer
1 ... 240
Please see chapter 4 for details.
30 sec
E.28
SERVICE A TIME :
Service A period
(Change air filter)
0 ...32767
If this parameter is set to 0 then service A
warning will not be given.
2000
hours
E.29
SERVICE B TIME :
Service B period
(Change oil filter)
0 ... 32767
If this parameter is set to 0 then service B
warning will not be given.
4000
hours
E.30
SERVICE C TIME :
Service C period
(Change separator filter)
0 ... 32767
If this parameter is set to 0 then service C
warning will not be given.
6000
hours