DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual
30 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
6.2 EDITING A VALUE
Oil pressure pre-alarm
Press the Stop/Reset and Info
i
buttons
simultaneously.
If the module PIN number has been set, the PIN number
request is then shown. The configuration cannot be viewed
or changed until the PIN number is correctly entered. (see
the section ACCESSING THE FRONT PANEL
CONFIGURATION EDITOR)
Press the + button until the desired page is shown. EG oil
ressure
re-alarm.
2 Bar 30 PSI
200 kPa
Oil pressure pre-alarm
To edit the oil pressure pre-alarm, press the 9 button, the
pressure will start to flash. Pressing the
+ or – buttons will
adjust the parameter to the desired value. In this example,
the 30 PSI will be adjusted, and the bar/kPA units will
automatically show their respective values.
2 Bar 30 PSI
200 kPa
Oil pressure pre-alarm
Press the 9 button to ‘save’ the value. The value will stop
flashing to confirm that it has been saved.
3 Bar 45 PSI
300 kPa
Oil pressure shutdown
To select another value to edit, press the + button.
1 Bar 15 PSI
100 kPa
NOTE:- To exit the front panel configuration editor at any time, press the Stop/Reset button.
Ensure you have saved any changes you have made by pressing the 9 button first.
Continuing to press the + or – buttons will cycle through the adjustable parameters in the order shown overleaf: