7 INSTALLATION INSTRUCTIONS
The model DSE 5310 Module has been designed for front panel mounting. Fixing is by 4 clips for easy assembly.
7.1 PANEL CUT-OUT
220.00mm
(8.7”)
FIG 3
Maximum panel thickness – 8mm (0.3”)
In conditions of excessive vibration the module should be mounted on suitable anti-vibration mountings.
7.2 COOLING
The module has been designed to operate over a wide temperature range -30 to +70º C. Allowances should be
made for the temperature rise within the control panel enclosure. Care should be taken
NOT to mount possible
heat sources near the module unless adequate ventilation is provided. The relative humidity inside the control
panel enclosure should not exceed
95%.
7.3 UNIT DIMENSIONS
Panel cutout 220mm x 160mm ( 8.7” x 6.3”)
FIG 4
160.00mm
(6.3”)