DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual
8 Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine
Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the
fault.
Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before
accepting the load.
If an auxiliary output has been selected to give a load transfer signal, this then activates.
NOTE:-A load transfer will not be initiated until the Oil Pressure has risen. Thus preventing
excessive wear on the engine.
On removal of the Remote Start signal, the Stop delay timer is initiated, once it has timed out, the load Transfer
signal is de-energised, removing the load. The Cooling timer is then initiated, allowing the engine a cooling down
period off load before shutting down. Once the Cooling timer expires the Fuel Solenoid is de-energised, bringing
the generator to a stop.
Should the Remote Start signal be re-activated during the cooling down period, the set will return on load.