Terminal Text Description
1 GND Power ground
2 BATT + Power supply positive
3 DIG OUT A DC output - A
4 DIG OUT B DC output - B
5 DIG OUT C DC output - C
6 DIG OUT D DC output - D
7 CHG ALT Input for charging alternator control
8 DIG OUT E DC output - E
9 DIG OUT F DC output - F
10 DIG IN A Input from switch A
11 DIG IN B Input from switch B
12 DIG IN C Input from switch C
13 CAN H CAN high
14 CAN L CAN low
15 B B
16 A A
17 Reserved -
18 Reserved -
19 Reserved -
20 Reserved -
21 DIG IN D Input from switch D
22 DIG IN E Input from switch E
23 ANLG - 20 Analogue input 4 to 20 mA
24 ANLG TEMP/DIG G Analogue input from the engine temperature sensor
25 ANLG FL/DIG H Analogue input from the fuel level sensor
26 ANLG/DIG F Analogue input from the sensor for the lube oil pressure
27 GENSET N Voltage input from generator neutral
28 GENSET L3 Voltage input from generator phase L3
29 GENSET L2 Voltage input from generator phase L2
30 GENSET L1 Voltage input from generator phase L1
31 MAINS N Voltage input from mains neutral
32 MAINS L3 Voltage input from mains phase L3
33 MAINS L2 Voltage input from mains phase L2
34 MAINS L1 Voltage input from mains phase L1
35 CT3 S2 CT input 2 from generator phase L3
36 CT3 S1 CT input 1 from generator phase L3
37 CT2 S2 CT input 2 from generator phase L2
38 CT2 S1 CT input 1 from generator phase L2
39 CT1 S2 CT input 2 from generator phase L1
User manual 4189341340A EN Page 10 of 76