3.5.7 Mains
Configuration (MAINS CONFIG)
Parameter Range Default Description
Mains Monitoring
Enable
Disable
Enabled
If this parameter is enabled, the controller
monitors the mains voltage and frequency.
Mains AC System
AC
1 phase
3 phase
3-phase Select the phase system for the mains.
Phase Reversal
Detection
REVERSAL
Enable
Disable
Not enabled
If this parameter is enabled, a phase reversal is
detected if the phase sequence is not
Phase Reversal Action
REVERSAL
None
Notification
None
Configure the action for phase reversal
detection.
Partial Healthy
Detection
PARTIAL
Enable
Disable
Not enabled
If this parameter is enabled, a mains failure is
not detected if one or two of the phases fail.
This is only for a 3-phase system.
Mains PT Enable
Enable
Disable
Not enabled
Enable this parameter, if the application
includes a mains power transformer
Mains PT Primary
PT
100 to 25000 100 Configure the PT primary value.
Mains PT Secondary
PT
100 to 700 100 Configure the PT secondary value.
Voltage Monitoring
(VOLT MONITOR)
Parameter
Range Default Description
Under-voltage
Enable
Disable
Yes
If this parameter is enabled, the controller
detects a mains failure when the mains voltage
is less than the under-voltage set point
trip).
Trip
50 to 298 V phase-
neutral
55 V
If the mains voltage is less than this set point,
there is a mains failure.
Return
52 to 300 V phase-
neutral
57 V
The mains returns when the mains voltage is
more than this set point.
Over-voltage
Enable
Disable
Yes
If this parameter is enabled, the controller
detects a mains failure when the mains voltage
is more than the over-voltage set point
trip).
Return
100 to 348 V phase-
neutral
280 V
If the mains voltage is more than this set point,
there is a mains failure.
Trip
102 to 350 V phase-
neutral
270 V
The mains returns when the mains voltage is
less than this set point.
Delay
0 to 100 s 10 s
If the voltage is more than the over-voltage set
point when this timer expires, the action for
over-voltage is activated.
User manual 4189341340A EN Page 32 of 76