4. Modes of operation
4.1 Operation mode
The controller has two running modes:
AUTO: The controller operates automatically, and the operator cannot initiate sequences manually.
Manual: The operator has to initiate all sequences. You can do this with the buttons, Modbus commands, or digital
inputs.
4.2 AUTO mode
In AUTO mode, you can select these functions:
Island
Engine drive
Automatic Mains Failure 
Remote start/stop
Auto exercise
If the controller is not in AUTO mode, push the mode selection button to change the running mode to AUTO.
4.2.1
Island
The controller operates in island when:
Mains monitoring is not enabled.
Auto exercise is not enabled.
In the smart connect software, go to Mains > Configuration > Mains monitoring and make sure that mains
monitoring is not enabled. To make sure that auto exercise is not enabled for events 1 and 2, go to Module > Auto
Exercise > Event 1/Event 2.
The controller automatically starts the genset and closes the generator breaker at a digital start command. When the stop
command is given, the generator breaker opens, and the genset is stopped after a cooling down period.
Use a digital input to activate and deactive the start and stop commands. You cannot use the display buttons in AUTO
mode.