Deif SGC 120 - Breakers; Breaker Types; Breaker Spring Load Timer

Deif SGC 120
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Text Range Default Note
Nominal load current 0 to 8000 A 350 A
Check the minimum and maximum values the SGC
can read and display. Remember to include the
CT.
Nominal 4th CT current 0 to 8000 A 800 A
Check the minimum and maximum values the SGC
can read and display. Remember to include the
CT.
Nominal speed 100 to 4000 RPM 1800 RPM
Check the minimum and maximum values the SGC
can read and display.
Nominal power (kW) 10 to 2000 kW 200 kW
Check the minimum and maximum values the SGC
can read and display. Remember to include the
PT.
5.3 Breakers
5.3.1 Breaker types
There are 2 breaker type settings.
Pulse
This setting is for breakers that have 2 separate coils for opening and closing the breaker.
The controller uses these outputs:
To close the circuit breaker, the Close Gen breaker output is activated. The output is active until the Breaker Close Pulse
timer expires. You can configure a digital input as Breaker Close Feedback and a Breaker Feedback timer. If the
controller does not receive feedback before the Breaker feedback timer expires, a Close Failure alarm is shown. If
Breaker Close Feedback is not configured, then an alarm is not shown.
To open the circuit breaker, the Open Gen breaker output is activated. The output is active until the Breaker Open Pulse
timer expires. You can configure a digital input as Breaker Open Feedback and a Breaker Feedback timer. If the controller
does not receive feedback before the Breaker feedback timer expires, an Open Failure alarm is shown. If Breaker Open
Feedback is not configured, then an alarm is not shown.
Continuous
This setting is for breakers that have a single coil for opening and closing the breaker.
The controller uses these outputs:
To close the circuit breaker, the Close Gen Output is activated. You can configure a digital input as Breaker Close
Feedback and a Breaker Feedback timer. If the controller does not receive feedback before the Breaker feedback timer
expires, a Close Failure alarm is shown. If Breaker Close Feedback is not configured, then an alarm is not shown.
To open the circuit breaker, the Open Gen Output is activated. You can configure a digital input as Breaker Open
Feedback and a Breaker Feedback timer. If the controller does not receive feedback before the Breaker feedback timer
expires, an Open Failure alarm is shown. If Breaker Open Feedback is not configured, then an alarm is not shown.
Timers > General
Parameter
Range Default
Breaker feedback Timer 1 to 10 s 2 s
5.3.2 Breaker spring load timer
To avoid breaker close failures in situations where the breaker close command is given before the breaker spring has been
loaded, the spring load timer can be adjusted. You can do this with the Breaker Close Delay timer.
User manual 4189341340A EN
Page 48 of 76