Frequency Monitoring (FREQ MONITOR)
Parameter Range Default Description
Under-frequency
Enable
Disable
Yes
If this parameter is enabled, the controller
detects a mains failure when the mains
frequency is less than the under-frequency set
point trip).
Trip
10.0 to 59.0 Hz 45 Hz
If the mains frequency is less than this set
point, there is a mains failure.
Return
11.0 to 60.0 Hz 47 Hz
The mains returns when the mains frequency is
more than this set point.
Over-frequency
Enable
Disable
Yes
If this parameter is enabled, the controller
detects a mains failure when the mains
frequency is more than the over-frequency set
point trip).
Return
25.0 to 74.0 Hz 55 Hz
If the mains frequency is more than this set
point, there is a mains failure.
Trip
26.0 to 75.0 Hz 52 Hz
The mains returns when the mains frequency is
less than this set point.
Delay 10 s
If the frequency is more than the over-
frequency set point when this timer expires, the
action for over-frequency is activated.
3.5.8 Engine
Crank Disconnect (CRANK DISCONN)
Parameter
Range Default Description
Start Attempts
1 to 9 3 Number of attempts to crank the engine.
Disconnect on Oil
Pressure Sensor
ON LOP
Enable
Disable
Not enabled
If this parameter is enabled, the crank is
disconnected when the oil pressure is more
than the oil pressure set point LOP
Monitor Pressure
Sensor Before Crank
LLOP BEF
Enable
Disable
Not enabled
If this parameter is enabled, the oil pressure is
monitored before the engine starts. If the oil
pressure is more than the set point LOP
BEF the engine cannot start.
Pressure Sensor
Monitoring Threshold
LOP
0.5 to 10.0 bar 4 bar Configure the set point for the oil pressure.
Monitor Pressure
Switch Before Crank
LOP BEF
Enable
Disable
Not enabled
If this parameter is enabled, the oil pressure is
monitored before the engine starts. If the
pressure switch is open, the controller activates
a high oil pressure alarm.
Disconnect on Oil
Pressure Switch
ON LLOP
Enable
Disable
Not enabled
If this parameter is enabled, the crank
disconnects if the oil pressure is high.
Pressure Switch
Transient Time
SW TRANS
0.0 to 3.0 s 1.5 s
If the oil pressure is high after this timer
expires, the crank is disconnected.