6.3 Engine stop functions
6.3.1 Stop sequence
The stop sequence is activated if a stop command is given. The stop sequence includes the cooling down time if the stop is
a normal or controlled stop.
Timers > General
Parameter
Range Default
Engine Cooling Time 0 to 300 s 5 s
Stop Action 10 to 120 s 10 s
Additional Stopping Time 0 to 120 s 10 s
Engine > Speed Monitoring
Parameter
Range Default
Stopping Idle Time 0 to 1200 s 10 s