Stop sequence for idle mode
You can also activate idle mode during the stop sequence. Go to Engine > Speed Monitoring > Stopping Idle Time
to configure the timer for the idle stop time. If you set the timer to 0 seconds, idle mode is not activated during the stop
sequence. The under-voltage, under-frequency, and under-speed protections are not active in idle mode.
When the stop sequence for the genset is activated, the Stopping Idle Time timer starts. When the timer expires, the genset
stops.
Idle mode parameters
Parameter
Range Default
Idle Mode Enable
Enable
Disable
Not enabled
Idle Mode On
Enable
Disable
Not enabled
Idle Mode On Pulse
Enable
Disable
Not enabled
Idle Mode Off Pulse
Enable
Disable
Not enabled
Idle to Rated Delay Time 0 to 1200 s 10 s
Start-up Idle Mode Time 0 to 1200 s 10 s
Stopping Idle Mode Time 0 to 1200 s 10 s
Idle Mode Pulse Time 0 to 60 s 2 s
6.5 Coolant temperature
You can use the controller to control the coolant temperature of the engine.
By default, the coolant temperature is not enabled. To use this function, you must configure an analogue input as a
temperature sensor or use the Engine Control Unit 
Configure the coolant temperature sensor with the smart connect software:
1. If you use an analogue input:
a. Go the Analog Inputs tab and select Analog Input 3.
b. For Use input As select Engine Coolant Temperature Sensor in the drop-down list.
2. If you use an 
a. Go to the Engine tab and select Engine Control Unit (ECU).
b. For Engine type select the correct ECU. Do not select Conventional.
c. Make sure that the tick box next to Coolant temperature is selected.
User manual 4189341340A EN