3.5.4 Outputs
Outputs # (OUT #)
Parameter Range Default Description
Source
See Digital output
source selection in
this document
- Select an output source from the list.
On Activation
Energise
De-energise
De-energise
Select what the status of the output source is
when it is active. You can select if it is
energised or de-energised.
3.5.5 Timers
Cranking (CRANKING TIMERS)
Parameter
Range Default Description
Crank Hold Time
HOLD
1 to 15 s 5 s Configure for how long the engine cranks.
Crank Rest Time
REST
2 to 60 s 5 s The time between each crank.
Manual Start Delay
START
0 to 300 s 3 s
When this timer expires in manual mode, the
engine starts to crank.
Auto Start Delay
START
0 to 43200 s 3 s
When this timer expires in AUTO mode, the
engine starts to crank.
General (GENERAL TIMER)
Parameter
Range Default Description
Safety Monitoring
Delay
MONITOR
10 to 60 s 10 s
The engine safety parameters are not
monitored during the Safety monitoring delay.
The timer starts after crank disconnect.
Warm-Up Delay
0 to 60 s 3 s
When the alternator voltage and frequency are
OK, the load is transferred to the alternator.
There's a warm-up delay before the load is
transferred.
Return To Mains Delay
0 to 600 s 5 s
The controller closes the mains breaker when
the return to mains delay timer expires.
Engine Cooling Time
COOL
0 to 300 s 5 s
When the engine cooling timer expires, the
engine stops.
Stop Action Time
ACTION
10 to 120 s 30 s
The time duration for the stop action sequence.
Additional Stopping
Time
STOPPING
0 to 120 s 10 s
Additional time added to the engine stop
sequence.
Load Transfer Delay
TRANSFER
0 to 60 s 1 s
The time it takes to transfer the load to the
mains or genset.
Power Save Mode
Delay
5 to 1800 s 30 s
If the controller is not in use, then the backlight
turns off when the timer expires.